Study on thermal performance of double-turbine regeneration system in double-reheat unit
Thermal Power GenerationVol. 46, Issue 8, Pages: 59-63(2017)
更新时间:2025-05-30
分享给微信好友或者朋友圈
导出参考文献
Study on thermal performance of double-turbine regeneration system in double-reheat unit
作者机构:
神华国华(北京)电力研究院有限公司
作者简介:
基金信息:
DOI:
CLC:TM621
Published:2017
稿件说明:
移动端阅览
QIAO Jiafei, ZHANG Lei, LIU Yinghua, et al. Study on thermal performance of double-turbine regeneration system in double-reheat unit[J]. Thermal Power Generation2017, 46(8): 59-63.
DOI:
QIAO Jiafei, ZHANG Lei, LIU Yinghua, et al. Study on thermal performance of double-turbine regeneration system in double-reheat unit[J]. Thermal Power Generation2017, 46(8): 59-63.DOI:
Study on thermal performance of double-turbine regeneration system in double-reheat unit
摘要
针对我国二次再热机组回热系统不可逆换热损失大等问题
在典型二次再热机组热力系统分析的基础上
重点分析了新型双机回热系统的热力性能
并将其与无前置蒸汽冷却器(蒸冷器)方案和增设前置蒸冷器方案进行了比较研究。结果表明
前置蒸冷器方案虽然可以降低2、4号高压加热器(高加)的过热度
但本质却是将其不可逆损失转移到了前置蒸冷器中
整个回热系统的?损降低有限。双机回热方案可以改善整个给水系统和除氧器的换热效果
显著降低2—4号高加以及除氧器的抽汽过热度
上述设备?效率均达到0.96以上
总?损比无前置蒸冷器方案降低了53%
比增设前置蒸冷器方案降低了51%。研究结果可为后续提高二次再热回热系统换热质量和机组性能提供借鉴。
Abstract
In view of the high superheat degree of bleeding steam in double-reheat units
thermal performance of high pressure heaters and deaerator was compared among the double-turbine regeneration system
regeneration system without outer steam cooler and regeneration system with outer steam cooler. Study shows that the superheat degree of No.2 and No.4 high pressure heaters is lower in the system with outer steam cooler
but the exergy loss of the whole regeneration system doesn't decline obviously. The result indicates that the superheat degree of No.2 to No.4 high pressure heaters and deaerator decline notably in double-turbine regeneration system
and the exergy efficiency of these heaters are all over 0.96. Compared with the regeneration system without outer steam cooler
the exergy loss in double-turbine regeneration system is reduced by 53%. Compared with the regeneration system with outer steam cooler
the exergy loss in double-turbine regeneration system is reduced by 51%. The results cloud be a reference for improving the regeneration efficiency and unit performance of double-reheat units.
Thermal economy research for double-reheat unit equipped with heat recovery steam turbine
CORRELATION BETWEEN TEST COEFFICIENTS OF INDUSTRIAL COOLING TOWER AND SIMULATED TESTING TOWER
MEASUREMENT AND CALCULATION METHOD FOR THERMAL PERFORMANCE TEST OF ULTRA-SUPERCRITICAL UNIT WITH STEAM TURBINE EQUIPPED WITH DOUBLE-ROW HIGH-PRESSURE HEATERS
Thermal economic analysis on an ultra supercritical unit with second reheat cycle
Performance study on water drenching filler with modified small spacing in cooling towers
Related Author
CUI Guangming
LIU Jiping
HU Sanji
CHEN Yuling
SHI Yan-zhou
ZHU Li-tong
YAO Xiao-lin
ZHONG Ping
Related Institution
Xi'an Thermal Power Research Institute Co., Ltd
School of Energy and Power Engineering, Xi'an Jiaotong University
School of Environmental Science and Engineering, Chang'an University
College of Energy, Power and Mechanical Engineering, North China Electric Power University
Key Laboratory of Power Station Equipment Status Monitoring and Control, Ministry of Education, North China Electric Power University