CHARACTERISTIC ANALYSIS OF TUBE-BURST OCCURRED ON HEATING SURFACE OF THE WATER-WALL IN 300 MW CFB BOILER
The situation of tube-burst occurred on the water-wall of 300 MW circulating fluidized bed(CFB) boilers has been presented.It is believed from analysis that the main causes are as follows:(1) untightness of the hand-operated valve for purging the tapered valve of slag-cooler at the right side of boiler no.1 by using compressed air;(2) unwelded fins of extended wall on the water-wall of boiler no.2;(3)the temporary weldments haven't removed;(4) long term scouring by hot air and other materials.For these
corresponding treatment and preventive measures have been put forward.
ANALYSIS OF TUBE-BURST FAILURE ON WATER-WALL IN BOILERS FOR SUBCRITICAL 300 MW UNIT
FLOW RATE DEVIATION IN THE WATER-WALL AND OVERTEMPERATURE TUBE-BURST THEREOF
CONTROL STRATEGY OF 300 MW UNITS EQUIPPED WITH CFB BOILERS
CLOSED-LOOP CONTROL SYSTEM OF CFB BOILERS
PRELIMINARY ANALYSIS OF REQUIREMENTS TO WATER-WALL SYSTEM PERFORMANCE FOR SERVICE OPERATION OF SUPERCRITICAL PRESSURE ONCETHROUGH BOILER OF 600MW UNITS
Related Author
LIU Bing1
ZHENG Fang-ping2
ZHANG Lei2
LIU Shu-tao21.Datang Huayu Power Generation Co Ltd
WANG Chun-changXi'an Thermal Power Research Institute Co Ltd
MEI Sheng1
HAO Defeng2 1.Ma'anshan Wannengda Power Generation Co Ltd