Cause analysis for tube burst of water wall in a subcritical 300 MW unit boiler
Water wall tube burst occurred in a subcritical 300 MW unit boiler. To find out the reasons
the macro characteristics of the rupture area were examined and the material's metallographic structure was analyzed by optical microscope
the energy dispersive spectroscopy(EDS) and X-ray diffraction(XRD) were adopted to examine the scale(corrosion products) on the tubes. The results show that
the tube exhibited "window opening"brittle fracture
and thick scale formed on inner wall of the fire-facing side. The substrate under scale was obviously thinned by corrosion
and decarbonization and intergranular crack were evident at the base metal. The rupture failure was resulted from hydrogen corrosion under scale. To insure the unit operation safety
several suggestions were put forward
such as preventive measures including using nondestructive testing method to examine the water wall tube
changing tubes with defects
conducting examination test to effectively decrease the scaling rate of the inner wall of water wall tube
and enhancing the monitoring of steam water quality.