Influence of desuperheating water of extraction steam on thermal performance of cogeneration units
The use of desuperheating water for extraction steam has a certain influence on thermal performance of the units
but the research on this aspect is relatively less. Taking a 330 MW cogeneration unit as an example
two schemes of extraction steam desuperheating with desuperheating water intake located at the outlet of condensate pump(scheme 1) and the place between No. 6 and No. 7 low pressure heaters(scheme 2) are compared by using the software EBSILON. The results show that
no matter the temperature of desuperheating water is high or low
as long as the desuperheating water is used
the coal consumption rate of the unit will increase
but the increment of coal consumption rate can be reduced by using desuperheating water with higher temperature. Under the rated condition
the increase of coal consumption rate of scheme 2 is 52.1% lower than that of scheme 1. At the same time
the temperature of desuperheating water also has an effect on the increase of extraction steam at the same heating load. In addition
both the flow rate of desuperheating water and the increment of coal consumption rate increase at first and then decrease with the increase of heating load at a certain live steam flow rate. When the desuperheating water is used
the system analysis should be carried out. By selecting the desuperheating water reasonably
the daily operation load of the unit can effectively avoid the area with the largest coal consumption rate increment.
CORRELATION BETWEEN TEST COEFFICIENTS OF INDUSTRIAL COOLING TOWER AND SIMULATED TESTING TOWER
MEASUREMENT AND CALCULATION METHOD FOR THERMAL PERFORMANCE TEST OF ULTRA-SUPERCRITICAL UNIT WITH STEAM TURBINE EQUIPPED WITH DOUBLE-ROW HIGH-PRESSURE HEATERS
MODELING OF SPRAY DESUPERHEATER IN AN ULTRA SUPERCRITICAL ONCE-THROUGH BOILER
Energy saving analysis on waste heat recovery of circulating cooling water for heating
Performance study on water drenching filler with modified small spacing in cooling towers
Related Author
HU Sanji
CHEN Yuling
SHI Yan-zhou
ZHU Li-tong
YAO Xiao-lin
ZHONG Ping
AN Hong-xinXi'an Thermal Power Insititute Co Ltd
FANG Yanjun
Related Institution
Xi'an Thermal Power Research Institute Co., Ltd
School of Power and Mechanical Engineering, Wuhan University
School of Mechanical and Electronic Engineering, Shandong University of Science and Technology
China Electric Power Engineering Corporation
Shenhua Guohua (Beijing) Electric Power Research Institute Co., Ltd