WANG Lin, YANG Bo, GAO Jinghui, et al. Adjustment on reheat steam temperature for a 660 MW double-reheat boiler[J]. Thermal Power Generation2017, 46(8): 91-95.
WANG Lin, YANG Bo, GAO Jinghui, et al. Adjustment on reheat steam temperature for a 660 MW double-reheat boiler[J]. Thermal Power Generation2017, 46(8): 91-95.DOI:
The reheat steam temperature of China's firstly built double-reheat boiler is sharply lower than the design value. To solve this problem
the quality of coal as fired and the heat absorption capacity of the boiler heating surface was analyzed. Moreover
the flue gas recirculation thermal control scheme was improved. On this basis
the comprehensive temperature improvement scheme was proposed
including optimizing the coal mill combination type
regulating the burner elevation angle
increasing the over fired air volume
improving the soot-blower'sputting-in-service mode and adjusting the flue gas recirculation amount. Furthermore
the condition test to explore the effect of burner's swinging angle and flue gas recirculation fan speed on temperature of the first reheat and second reheat steam were carried out. After debugging optimization
the reheat steam temperature of the boiler can reach 610~620 ℃ at high load and 590~590 ℃ at low and medium loads
which are similar with the design value
indicating the problem of low reheat steam temperature was solved well. The debugging experience has project reference value for subsequent similar units.